1.0 Objective
1.1 To define a uniform procedure for operating
Munter’s dehumidifiers to ensure consistent and safe practices.
2.0 Scope
2.1 This SOP covers the operation of
Munter’s dehumidifiers at the Stalink Private Limited facility in as per place.
3.0 Responsibility
|
S. No |
Role |
Responsibility |
|
3.1 |
Engineering Personnel |
Responsible
for operating and monitoring the dehumidifiers. |
|
3.2 |
Engineering Head/ Designee |
Accountable for ensuring overall compliance with
this SOP. |
|
3.3 |
QA Head/ Designee |
Responsible for reviewing and approving this SOP. |
4.0 Definition
4.1 Not applicable
5.0 Safety and General Instruction
5.1 Operators must wear appropriate
personal protective equipment (PPE) — including gloves, safety goggles, and
safety shoes — and any additional PPE as required before operating the dehumidifier.
6.0 Procedure
Key points of SOP
• Open the main steam valve and ensure
steam pressure is maintained at a minimum of 5 kg/cm².
• Keep the chilled water inlet and outlet
valves of the pre-cooling unit closed.
6.1 Operation of Dehumidifier Make: Munter’s Model
6.1.1 Starting Procedure:
6.1.1.1 Verify that the associated AHU is
switched ON.
6.1.1.2 Turn ON the dehumidifier's main
power supply.
6.1.1.3 Select the Auto/Manual mode on the
control panel to initiate the dehumidifier.
6.1.1.4 Open both chilled water inlet and
outlet valves of the pre-cooling unit.
6.1.1.5 Drain condensate via the bypass
valve and close the valve after draining completes.
6.1.1.6 Open the main steam valve and confirm the
steam pressure is at least 5 kg/cm².
6.1.2 Stopping Procedure:
6.1.2.1 Press the OFF button to shut down
the dehumidifier.
6.1.2.2 Close the chilled water inlet and
outlet valves of the pre-cooling unit.
6.1.2.3 Close the main steam valve.
6.1.2.4 Record daily usage of the
dehumidifier in the 'Monitoring Record of Dehumidifier'.
6.1.2.5 If the unit runs continuously, enter 'RC' in
the Start/Stop column and provide additional details in Remarks.
6.2 Operation of Dehumidifier Make: Munter’s Model
6.2.1 Starting Procedure:
6.2.1.1 Verify that the associated AHU is
switched ON.
6.2.1.2 Turn ON the dehumidifier's main
power supply.
6.2.1.3 Press the START button on the
control panel to begin operation of the dehumidifier.
6.2.1.4 Open both chilled water inlet and
outlet valves of the pre-cooling unit.
6.2.1.5 Drain condensate via the bypass
valve and close the valve after draining completes.
6.2.1.6 Open the main steam valve and confirm the
steam pressure is at least 5 kg/cm².
6.2.2 Stopping Procedure:
6.2.2.1 Press the STOP button to stop the
dehumidifier.
6.2.2.2 Close the chilled water inlet and
outlet valves of the pre-cooling unit.
6.2.2.3 Close the main steam valve.
6.2.2.4 Record daily usage of the
dehumidifier in the 'Monitoring Record of Dehumidifier'.
6.2.2.5 If the unit runs continuously, enter 'RC' in
the Start/Stop column and provide additional details in Remarks.
7.0 Abbreviations
|
Abbreviation |
Meaning |
|
SOP |
Standard Operating Procedure |
|
EN |
Engineering |
|
QA |
Quality Assurance |
|
AHU |
Air Handling Unit |
|
RC |
Running Continuously |
|
WC |
Water Column |
|
Kg/cm² |
Kilogram per square centimetre |
|
DHU |
Dehumidifier Unit |
|
PPE |
Personnel Protective Equipment |